https://doi.org/10.1051/epjn/e2015-50006-1
Regular Article
Safety operation of chromatography column system with discharging hydrogen radiolytically generated
Japan Atomic Energy Agency, 4-33, Muramatsu, Tokai-mura, Naka-gun, Ibaraki 319-1194, Japan
* e-mail: watanabe.sou@jaea.go.jp
Received:
30
April
2015
Received in final form:
18
September
2015
Accepted:
5
October
2015
Published online:
9
December
2015
In the extraction chromatography system, accumulation of hydrogen gas in the chromatography column is suspected to lead to fire or explosion. In order to prevent the hazardous accidents, it is necessary to evaluate behaviors of gas radiolytically generated inside the column. In this study, behaviors of gas inside the extraction chromatography column were investigated through experiments and Computation Fluid Dynamics (CFD) simulation. N2 gas once accumulated as bubbles in the packed bed was hardly discharged by the flow of mobile phase. However, the CFD simulation and X-ray imaging on γ-ray irradiated column revealed that during operation the hydrogen gas generated in the column was dissolved into the mobile phase without accumulation and discharged.
© S. Watanabe et al., published by EDP Sciences, 2015
This is an Open Access article distributed under the terms of the Creative Commons Attribution License (http://creativecommons.org/licenses/by/4.0), which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.